Point Count doubles in V7.0 when a Cicode function for example TagRead() is called in the background or from kernel window. |
Solution: |
Citect Runtime by mistake treats the
calling of any tag using a Cicode function at the background or
through a kernel window as a second instance and there by doubles
the point count. Hotfix(HF700R136958) is available for this issue in V7. |