Summary:
Cannot Download Tags - SOAPAction: http://tempuri.org/WebCtFindProperties When I try to 'Download Tags' onto my PPC running Pocket SCADA, I get the following Error Message:

System.Web.Services.Protocols.SoapException:
Server did not recognize the value of HTTP Header SOAPAction: http://tempuri.org/WebCtFindProperties
at System.Web.Services.Protocols.Soap11ServerProtocolHelper.RouteRequest()
at System.Web.Services.Protocols.SoapServerProtocol.RouteRequest(SoapServerMessage Message)
at System.Web.Services.Protocols.SoapServerProtocol.Ini..........


Solution:

This was seen when running the incorrect version of CitectSCADA Pocket Client on the PPC/PDA. The version of the Pocket Client, was v6.0, whereas the Server was running v7.

The 'Tempuri' domain is a reserved domain for testing WebService applications, so this can be ignored.

Please note, that with v7, the name of the Pocket SCADA client was changed from 'PocketSCADA' to 'CitectSCADA Pocket'

NEW

OLD

   
      
If you have a previous version of Pocket SCADA Client installed, in order to remove all clashing instances of it, please follow the following steps

* Connect PDA/PPC to PC and Open ActiveSync
* Add/ Remove all instances of PocketSCADA, CitectSCADA Pocket
* In ActiveSync, click 'Explore', and delete the following files/folders if they still exist:
- 'My Windows Mobile-Based Device' | 'Program Files' | 'CitectSCADA Pocket'
- 'My Windows Mobile-Based Device' | 'Program Files' | 'PocketSCADA'
- 'My Windows Mobile-Based Device' | 'My Documents' | 'config.xml'

* Re-install the correct version of Citect SCADA Pocket.

This will ensure that no previous settings / installations will interfere.


Some other known errors are:
 

Could not find resource assembly

The network is down or the server URL in the setup page is blank. This can also occur if the web service takes too long to start up. Try logging in again or increase the Web Method Timeout

NotSupportedException

Server URL in the Setup page is not a valid URL

WebCtOpen failed to log on

The login username/password are not correct for the current Citect project or Citect is not running.

System.Web.Services.Protocols.SoapException: Server was unable to process request. ---> System.InvalidOperationException: No hardware lock present…

Pocket license was not found on the Citect key. Connect a key with a Pocket license and try logging in again.

Wrong password for Administrator

If you have forgotten the administrator password, see

 