Applies To:
  • VijeoCitect 7.0r3

I have defined a page using the XP-style templates, and SXGA resolution. When I try and compile my project, I receive a compile error:

"CSV_Nav_Help_HelpButtonClick() - function not defined"


The Help button on the "normal" template in the CSV_include project, XP Style,resolution "SXGA", calls the "CSV_Nav_Help_HelpButtonClick()" function. This function is indeed not defined. Using this template returns therefore a compile error. You should replace this function call with
CSV_Nav_Help() This problem will be fixed in a future release of the product. Note: this problem does not apply to CitectSCADA