Applies To: |
|
Summary: |
Using the IODeviceControl() Cicode function to disable then enable Modnet I/O Devices, Devices may not successfully re-establish communications to the PLC. |
Solution: |
Citect has confirmed this to be a problem in Modnet v2.06.06.001 and earlier. This problem has been fixed in v2.06.09.002. |
Keywords: |
Related Links
Attachments