Applies To:
  • CitectSCADA 5.31, 5.40, 5.41, 5.42, 5.50, 6.0, 6.1, 7.0

Summary:
When using the new line characters (^n) in the Comment field of a Variable Tag belonging to an ABCLX I/O Device will result in the ABCLX driver not being able to subscribe to all Variable Tags on start-up.  

Solution:

Citect has confirmed this to be a problem in ABCLX v3.02.37.001 and earlier. This problem has been fixed in v3.03.08.004.


Keywords:
 

Attachments