Applies To: |
|
Summary: |
When using the new line characters (^n) in the Comment field of a Variable Tag belonging to an ABCLX I/O Device will result in the ABCLX driver not being able to subscribe to all Variable Tags on start-up. |
Solution: |
Citect has confirmed this to be a problem in ABCLX v3.02.37.001 and earlier. This problem has been fixed in v3.03.08.004. |