Applies To: |
|
Summary: |
I get #comms on my graphic page with variable tags that have bit level addressing. E.g. The PLC address is Tag1 data type DINT. The corresponding Citect address is Tag1.1 data type DIGITAL |
Solution: |
As per the ABCLX help all the "." should be replaced with a "/". I.e. The Citect address should be changed from Tag1.1 to Tag1/1. If you have used "." then you may get the driver error 0x20000015 in the syslog.dat file. |