I am
trying to read register 432000 with Modbus v2.6.4.1, but the read
fails with an ErrDriver 258 (0x102).
However, I can read the 400000-416000 range properly. The help file mentions that the 400000-465536 is supported by the driver |
Solution: |
This is
a bug in Modbus v2.6.4.1, and was fixed in driver hotfix
v2.06.17.003. This driver allows reads for the 400000-465536 range.
This driver has yet to be officially released.
Please contact Citect Support to obtain the hotfix for the driver or for further information. |
Keywords: |
modbus, address out of range, high register, large address |