“On Page Exit” Event does not execute in V7.



An “On Page Exit” Event configured on popup page which is open by WinNewAt( ) or AssWin( ) does not execute when exiting the page.

This is a known issue in V7.

The work-around is to remove the “On Page Exit” Event and add the same functionality to the ‘close button’ on the page.

Citect has confirmed this to be a problem in CitectHMI/SCADA version 7.0. We are researching this problem and will post new information here as it becomes available.