Applies To: |
|
Summary: |
The [Debug]shutdown ini parameter has three
options: 0 - (The Shutdown option is not displayed) 1 - (The Shutdown option is displayed on the control menu) 2 - (The Shutdown option is displayed only on child graphics pages) It has been found that option 2 is not available from the Citect control menu when running the computer setup wizard. The only options available are option 0 and option 1, depending on whether you tick or untick the "shutdown menu" box This will result in [Debug]shutdown=0 or [Debug]shutdown=1 being set in the Citect.ini file |
Solution: |
To workaround this problem you will have to manually set [Debug]Shutdown=2 in the Citect.ini file each time you run the computer setup wizard, after restoring the projects which require this setting Please note that everytime you run the computer setup wizard, values for certain parameters in your Citect.ini file can be changed. |