Applies To:
  • CitectSCADA 5.31, 5.40, 5.41, 5.42, 5.50, 6.0, 6.1, 7.0
  • CitectHMI 5.31, 5.40, 5.41, 5.42, 5.50, 6.0, 6.1, 7.0
  • CitectFacilities 5.31, 5.40, 5.41, 5.42, 5.50, 6.0, 6.1, 7.0
  • CitectSCADA Batch 5.31, 5.40, 5.41, 5.42, 5.50, 6.0, 6.1, 7.0
  • CitectSCADA Pocket 5.31, 5.40, 5.41, 5.42, 5.50, 6.0, 6.1, 7.0

Summary:

Running through the communications setup wizard to create diskdrv devices will truncate the filename used if the device name is more than 8 characters. This will cause difficulties if multiple diskdrv devices have a filename which share the first 8 characters, and were created using this wizard. This is because in runtime changing tag values of one of these devices can inadvertently change unrelated tags of the other device.

 

Solution:

If you are creating diskdrv devices with using the wizard, and have an I/O device name longer than 8 characters, please double check the address field in the I/O devices form after running through the wizard (see Communications>I/O Devices in the Project Editor window). The address field should provide the full path and filename of the diskdrv device, here the filename can be edited to longer than 8 characters.

 

Keywords:
 