Applies To:
  • CitectSCADA 6.0, 6.1, 7.0
  • CitectHMI 6.0, 6.1, 7.0


You can load tags directly into the Instant Trend display by putting the mouse cursor on a tag value on a graphics page and pressing the plus (+) key.
However, this does not work on a webclient.


- You can call a Tag Selection dialog by right-clicking the Instant trend tag window.
- If you have configured many trend tags, the Tag Selection dialog may take a while to be populated. 
This can be avoided by setting [TrendX]TagListEnable=0. 
This will allow the user to manually type in their trend tag name without having to wait for the list of current tags to be loaded into the Tag Selection dialog.