Applies To:
  • CitectSCADA 7.0
  • CitectHMI 7.0
  • CitectFacilities 7.0


I get a compile error when I try to use D registers higher then 1023 with the MelsecAnA driver. Knowledge base article Q1682 states that the MelsecA driver has been superceded by the MelsecAnA driver.



The current MelsecAnA.DBF has the D register set to 1023 as the max value
In order to accomodate registers higher then 1023 we need to change this to 6143 as the max value.
This should allow us to use any D registers up to 6143