Applies To:
  • CitectSCADA 5.31, 5.40, 5.41, 5.42, 5.50, 6.0, 6.1, 7.0
  • CitectHMI 5.31, 5.40, 5.41, 5.42, 5.50, 6.0, 6.1, 7.0
  • CitectFacilities 5.31, 5.40, 5.41, 5.42, 5.50, 6.0, 6.1, 7.0
  • CitectSCADA Batch 5.31, 5.40, 5.41, 5.42, 5.50, 6.0, 6.1, 7.0
  • CitectSCADA Pocket 5.31, 5.40, 5.41, 5.42, 5.50, 6.0, 6.1, 7.0

Summary:

I get a popup error message: "ABSRLINX: MaxPending is too large for the number of ports" when I start up my project.

 

Solution:

There is a relationship between the number of RSLINX ports defined in the project and the value of MaxPending set for the ABRSLINX driver.

Number of RSLinx ports * MaxPending has to be smaller or equal to 40.

 

Keywords:
 