Applies To:
  • CitectSCADA 7.0
  • CitectHMI 7.0
  • CitectFacilities 7.0

Summary:
I have upgraded my project to v7 and I have given my servers the following names:
IO Server = “IO_Server”
Report Server = “Report_Server”
Alarm Server = “Alarm_Server”
Trend Server = “Trend_Server”
When I come to compile my project I get compile errors: “Tag Expected” and “A server with this name already exists”. Looking over the server configuration I don’t see anything wrong. How do I remove these compile errors?  

Solution:

In Citect version 7.0 labels have been added to the Include project corresponding to the server names configured above. The label “Client” has also been used.

To resolve this change the name of your Report / Alarm / Trend / IO Server so that it doesn’t clash with these names, for example: IOServer, ReportServer, AlarmServer, TrendServer.

 

Keywords:
 

Attachments