Applies To:
  • CitectSCADA 6.0, 6.1, 7.0
  • CitectHMI 6.0, 6.1, 7.0
  • CitectFacilities 6.0, 6.1, 7.0


The Standard CSV_include trend pages have the functionality to create and retrieve predefined trend groups.  When a group is selected the tags in that group are loaded into the standard trend page together.  This is great feature but the trend groups are not available when running Citect in a web client. 


The trend groups are recorded in a dbf device file stored in the project directory.  Because a web preparation only includes the runtime files the dbf files are not automatically included in the web preparation.  The way around this is to manually add the trendgrp.dbf file into the following zip archive after creating the web preparation but before deploying to the web server.

...User\<compile project>\webdeploy\