Summary:
The Help for the Kingfish driver describes how to configure for a serial connection. I would like to use the TCPIP connection available on our Kingfish device. What are the boards and ports settings for a TCPIP connection to a Kingfisher RTU? 

Solution:

Boards:
Board Type:
TCPIP

Address:
0

I/O Port
Blank

Interrupt
Blank

Special Option
Blank

 

Ports:
Port Name;
Any unique name

Port Number:
Any unique number

Board Name:
The TCPIP board described above on the same IOserver

Baud Rate:
Blank

 

Data Bits:
Blank

Stop Bits:
Blank

Parity:
Blank

Special Options:
-i<IP address> -p<port number>
For example…    -i10.127.1.0 -p473

IO device:
The same as for serial coms, see the KB Q3948 for redundant Ethernet IO device addresses.

For example
IOServerA - Primary Device
202,0,0xfe

IOServerB - Standby Device
202,0,0xff 


Applies To:
  • CitectSCADA 5.31, 5.40, 5.41, 5.42, 5.50, 6.0, 6.1, 7.0
  • CitectHMI 5.31, 5.40, 5.41, 5.42, 5.50, 6.0, 6.1, 7.0
  • CitectFacilities 5.31, 5.40, 5.41, 5.42, 5.50, 6.0, 6.1, 7.0
  • CitectSCADA Batch 5.31, 5.40, 5.41, 5.42, 5.50, 6.0, 6.1, 7.0
  • CitectSCADA Pocket 5.31, 5.40, 5.41, 5.42, 5.50, 6.0, 6.1, 7.0
Keywords:
 Kingfisher RTU TCPIP

Attachments