Applies To:
  • CitectSCADA 7.0, 7.1
  • CitectHMI 7.0, 7.1
  • CitectFacilities 7.0, 7.1
  • VijeoCitect 7.0, 7.1


I get a "Tag Expected" compile error while compiling a V7 project and if I click on Goto in the compile error it takes me to the Servers form. 


The issue is caused by the naming convention used in V7 for example if you have defined your Alarm, Trend or Report Server Names as Alarm_Server, Trend_Server or Report_Server correspondingly you get this compile error. Adding [General]TagstartDigit =1 does NOT fix the issue. The only option is to change the server names to a different name.