Applies To:
  • CitectSCADA 5.31, 5.40, 5.41, 5.42, 5.50, 6.0, 6.1, 7.0
  • CitectHMI 5.31, 5.40, 5.41, 5.42, 5.50, 6.0, 6.1, 7.0
  • CitectFacilities 5.31, 5.40, 5.41, 5.42, 5.50, 6.0, 6.1, 7.0
  • VijeoCitect 5.31, 5.40, 5.41, 5.42, 5.50, 6.0, 6.1, 7.0

Summary:

Old alarm instances in Alarm Summary Page change to current date when the alarm is triggered again with the current date. To reproduce the Issue run the project and trigger some alarms and trigger the same alarms with a different date you can see that the older instances of the alarms in the Alarm Summary page change to the new date as well. 


Solution:

This issue is caused if you have defined the {DATE,10} in your Summary Format Field in the Alarm Categories. Please note {DATE,..} is not a valid format field for Summary format, its valid only for Alarm Format. The field should be {ONDATE,..} and {OFFDATE,..} for the Summary format. 


Keywords:
 