Applies To: |
|
Summary: |
Compiling a project that has multiple alarm categories with the same category number does not produce a compile error. |
Solution: |
With the introduction of multi-cluster in V7, most of the
project settings (tags, servers etc) are tied to a cluster,
however, alarm category is NOT confined to a cluster. In a group of
projects or clusters, the alarm category must be unique, i.e.: if
category1 is defined in cluster1, it can not be used again in
cluster2 etc. |
Keywords: |
Related Links