I am able to read tags from the PLC but I cannot write to them. The ABCLX IOdevice is configured properly and this issue affects any tags defined in the database. The syslog.dat file shown the following error: Generic 000008 Driver 536870933 (0x20000015) |
Solution: |
Please ensure that an user is currently logged in the Citect system. Citect v7.10 now required an user to be logged in to issue a control action. If you wish to return to the functionnality of previous versions of CitectSCADA (Where a login is not required), please add the following parameter to the Citect.ini file: [LAN] SecureLogin = 0 (Default value 1) |