Unable to write to .delay value of a Digital Alarm Tag when "Alarm Properties as tags" are used. For Example; using TagDebug() form and writing to the AlarmTagName.Delay value will result in a Hardware alarm: "PLC Server Write location is protected". Changing the Citect.ini parameters and deleting the AlarmSave.DAT files did not resolve the problem: [Alarm]UseConfigLimits |
Solution: |
A workaround exists for this issue by using the AlarmSetDelay() / AlarmGetDelay() cicode functions. The issue is currently being investigated. Please contact Support for additional information. |