From the driver
help:
MODNET - 1-indexed registers/coils with bit
access to registers as 1-16.
No support for extended registers.
Maximum request size of 2000 bits.
MODNET0 - 1-indexed registers/coils with bit access
to registers as 1-16.
No support for extended registers.
Maximum request size of 2000
bits.
MODNET1 - 0-indexed registers/coils with bit access
to registers as 1-16.
No support for extended registers.
Maximum request size of 2000 bits.
MODNET2 - 1-indexed registers/coils with bit access
to registers as 0-15.
No support for extended registers.
Maximum request size of 2000 bits.
MODNET3 - 0-indexed registers/coils with bit access
to registers as 0-15.
No support for extended registers.
Maximum request size of 2000 bits.
MODNET10 - 1-indexed registers/coils with bit access to
registers as 1-16.
Support for extended registers.
Maximum request size of 1920 bits.
MODNET11 - 0-indexed registers/coils with bit access to
registers as 1-16.
Support for extended registers.
Maximum request size of 1920 bits.
MODNET12 - 1-indexed registers/coils with bit access to
registers as 0-15.
Support
for extended registers.
Maximum
request size of 1920 bits.
MODNET13 - 0-indexed registers/coils with bit access to
registers as 0-15.
Support for extended registers.
Maximum request size of 1920 bits.
MODNET20 - TSX Quantum Compatability Mode.
1-indexed registers/coils with bit access to registers as
0-15.
Support for extended registers.
Maximum request size of 1920 bits.
Forced parameter: RegisterBitReverse=1, FloatMode=0,
LongDataType=3
MODNET21 - TSX Quantum Compatability Mode. (superseded by
MODNET20)
1-indexed registers/coils with bit access to registers as
0-15.
No support for extended registers.
Maximum request size of 2000 bits.
Addressing syntax %M123, %MW123, %MW123.4 etc...
Forced parameter: RegisterBitReverse=1, FloatMode=0,
LongDataType=3
MODNET30 - TSX Premium Compatability Mode.
0-indexed
registers/coils with bit access to registers as 0-15.
No
support for extended registers.
Maximum
request size of 1024 bits.
Forced parameter: RegisterBitReverse=1, FloatMode=0,
LongDataType=3
MODNET31 - TSX Premium Compatability Mode. (superseded by
MODNET30)
0-indexed
registers/coils with bit access to registers as 0-15.
No
support for extended registers.
Maximum
request size of 1024 bits.
Addressing syntax %M123, %MW123, %MW123.4 etc...
Forced parameter: RegisterBitReverse=1, FloatMode=0,
LongDataType=3
|