Applies To:
  • CitectSCADA

 When using the Unity Speedlink tool to import tags from OFS into Vijeo Citect, you may find that you have too many tags being created in your variable tag database.

The additional tags being imported are the "Specific Items" defined within the OFS Server.  To disable these "Specific Items" from being imported into the Variable Tag Database:

1.)  Open the OFS Configuration Tool
2.)  Navigate to the OFS Server Settings / Communications Settings
3.)  Uncheck the box in the Settings for Specific Items "Enable OPC Extensions

Now when you import the tags, the specific items will not get imported.


<Image Attached>