Applies To: |
|
Summary: |
When InfoForm() function is called it shows
a dialog box with twice the name and values of
Eng_full instead of showing Eng_Zero and Eng_Full.![]() |
Solution: |
Goto: Project: Include File: Info.ci Function:InfoFormAn() Line Number 438 -> cicode editor -> EDIT > Go to Line _InfoField( 0, 6, 8, 10, 22); !Eng Zero has to be changed to _InfoField( 0, 6, 7, 10, 22); !Eng Zero After Changes: ![]() This issue has been fixed in CitectSCADA version 7.1 spk 2.0. |
Keywords: |
InfoForm, Eng_Full, Eng_Zero |