Applies To:
  • CitectSCADA V7.1

Summary:
When InfoForm() function is called it shows a dialog box with twice the name and values of Eng_full instead of showing Eng_Zero and Eng_Full.


  

Solution:
Goto:

Project: Include
File: Info.ci
Function:InfoFormAn()

Line Number 438 -> cicode editor -> EDIT > Go to Line

_InfoField( 0, 6,  8, 10, 22);  !Eng Zero

has to be changed to _InfoField( 0, 6,  7, 10, 22); !Eng Zero

After Changes:



This issue has been fixed in CitectSCADA version 7.1 spk 2.0.

Keywords:
 InfoForm, Eng_Full, Eng_Zero

Attachments