Applies To:
  • CitectSCADA v6.x, v7.x

 I am trying to install the User & Data directories of CitectSCADA on a mapped drive. I have all the Windows privileges to read and write on this mapped drive (Full Access), but I am getting an installation error. (Error 1926)

  A workaround to this issue is to install the User and Data directory on the local drive. Once Citect is installed, follow the steps below:

-          Move the User and Data directories to the Mapped drive

-          Edit the Citect.ini file and change the User and Data paths in the [CtEdit] section

-          Edit the Master.DBF file located in the User folder and change all the project’s paths

 Installation, Error 1926, Mapped drive