Applies To:
  • CitectSCADA Version 7.10 

Summary:
HF710R143097 for CitectSCADA Version v7.10

Bug 43097 - IO Redundancy doesn't fail over until the primary server is completely shutdown.

Some systems will notice an extended delay (often 10 to 15 or more seconds) when switching from an active I/O server to a secondary I/O server when the SCADA system is shutdown cleanly.  This was caused by the networking layer not being shutdown at an appropriate point in the shutdown sequence. This issue has now been fixed.

Files Affected:
Client.dll                                  copy to _ProgramFilesFolder_\Citect\CitectSCADA 7.10\Bin\Client.dll
IOConnectors.dll                            copy to _ProgramFilesFolder_\Citect\CitectSCADA 7.10\Bin\IOConnectors.dll
IoServer.dll                                copy to _ProgramFilesFolder_\Citect\CitectSCADA 7.10\Bin\IoServer.dll
Citect.Platform.Net.SessionManager.dll      Install using HF710R143097.bat
Citect.Platform.Net.Session.Tcpip.dll       Install using HF710R143097.bat
Citect.Platform.PSI.Connector.dll           Install using HF710R143097.bat
CitectSCADAWebClient_7_10_0_10015.Cab       Web Server/Client