HF710R143097 for CitectSCADA Version
v7.10 Bug 43097 - IO Redundancy doesn't fail over until the primary server is completely shutdown. Some systems will notice an extended delay (often 10 to 15 or more seconds) when switching from an active I/O server to a secondary I/O server when the SCADA system is shutdown cleanly. This was caused by the networking layer not being shutdown at an appropriate point in the shutdown sequence. This issue has now been fixed. |
Files Affected: |
Client.dll copy
to _ProgramFilesFolder_\Citect\CitectSCADA
7.10\Bin\Client.dll IOConnectors.dll copy to _ProgramFilesFolder_\Citect\CitectSCADA 7.10\Bin\IOConnectors.dll IoServer.dll copy to _ProgramFilesFolder_\Citect\CitectSCADA 7.10\Bin\IoServer.dll Citect.Platform.Net.SessionManager.dll Install using HF710R143097.bat Citect.Platform.Net.Session.Tcpip.dll Install using HF710R143097.bat Citect.Platform.PSI.Connector.dll Install using HF710R143097.bat CitectSCADAWebClient_7_10_0_10015.Cab Web Server/Client |