Applies To:
  • CitectSCADA

Summary:
Some of ini parameters in Modbus20, Modbus30, Modnet20 and Modnet30 are hardcoded in the driver and these parameters cannot be changed by the user.

Solution:
Please refer to the list below for the parameter that are hardcoded in the driver. Please note that even if the User adds a different value to these parameters in the ini file it does NOT have any effect in the operation.

Modnet20(quantum):
MaxBits=2000
MaxBitsExt=1920
RegisterBitReverse=1
FloatMode=0
LongDataType=3

Modnet30(premium):
MaxBits=1024
MaxBitsExt=1024
RegisterBitReverse=1
FloatMode=0
LongDataType=3

Modbus20(quantum):
MaxBits=1904
MaxBitsExt=1904
RegisterBitReverse=1
FloatMode=0
LongDataType=3

Modbus30(premium):
MaxBits=1024
MaxBitsExt=1024
RegisterBitReverse=1
FloatMode=0
LongDataType=3

Keywords:
Modnet20, Modnet30, Modbus20, Modbus30