Applies To: |
|
Summary: |
Some of ini parameters in Modbus20, Modbus30, Modnet20 and Modnet30 are hardcoded in the driver and these parameters cannot be changed by the user. |
Solution: |
Please refer to the list below for the
parameter that are hardcoded in the driver. Please note that even
if the User adds a different value to these parameters in the ini
file it does NOT have any effect in the operation. Modnet20(quantum): MaxBits=2000 MaxBitsExt=1920 RegisterBitReverse=1 FloatMode=0 LongDataType=3 Modnet30(premium): MaxBits=1024 MaxBitsExt=1024 RegisterBitReverse=1 FloatMode=0 LongDataType=3 Modbus20(quantum): MaxBits=1904 MaxBitsExt=1904 RegisterBitReverse=1 FloatMode=0 LongDataType=3 Modbus30(premium): MaxBits=1024 MaxBitsExt=1024 RegisterBitReverse=1 FloatMode=0 LongDataType=3 |
Keywords: |
Modnet20, Modnet30, Modbus20, Modbus30 |