Applies To:
  • CitectSCADA
  • VijeoCitect
  • CitectFacilities

Modnet Protocol debugging seems to have changed with Modnet driver version and above. Having

DebugStr = * all

only returns request traces, whereas previously we could see the response traces as well

Due to some change in the driver code base for response traces, we are now only able to see the request part of traces from modnet protocol debugging. To view response traces and some extended debug information please use following INI parameters

DebugStr = * all
Debug = 1

Currently this change only effects driver versions

Modnet V2.06.09.002
Modnet V2.06.19.000


 DebugStr, Modnet