Applies To: |
|
Summary: |
OPC versions between v1.17.12.x and
v2.0.3.x could fail to connect to some OPC servers, e.g. OPC
DataHub. This occured when the handle returned by the Server,
allowed "0" to be a valid handle. Thus tags from this server would
show as #COM. (OPC traces with "Server Handle: 0x00000000" in them would be the clue) |
Solution: |
This problem has been solved in v2.0.4.x and is available as a Hotfix on request. |
Keywords: |
OPC Connection |
Related Links
Attachments