  • CitectSCADA v7.00 spk 2 
Summary:

HF700SP244589 for CitectSCADA Version 7.00 Service Pack 2

Bug 43311 - The file 'AlmIndexSave.dat' was corrupt or invalid after deleting and adding alarms

Previously alarm index file corruption can be caused by adding and removing alarms from the project
and then starting Citect. The problem is related to the deleted alarm ids being re-used by the newly
created alarms. This has now been resolved.


Bug 43427 - Since Service Pack 1, reports require an output device to run cicode in a report file.

Previously the Reportserver will not run (execute reports) when an Output device has not been specified
in the reports form. This has now been resolved.


Bug 44720 - When using background polling, Acknowledged ON alarms need to be reacknowledeged after
a restart

The IOServer code has been changed so that alarm values have an initial quality of
GENERIC_UPDATE_INPROGRESS rather than GENERIC_NOERROR. This means that all tag values will not
return good quality data by default.


Files Affected:
AlarmServer.dll         copy to Program Files\Citect\CitectSCADA 7\Bin
PolledDataSource.dll    copy to Program Files\Citect\CitectSCADA 7\Bin
ReportServer.dll        copy to Program Files\Citect\CitectSCADA 7\Bin
IOServer.dll            copy to Program Files\Citect\CitectSCADA 7\Bin