Applies To: |
|
Summary: |
I would like to use the MELSECQ driver to talk to a Mitsubishi Q03UDECPU PLCs is this possible and how do I set this up? |
Solution: |
It is possible to use the MELSECQ
driver since the QnUDE(H) uses the QnA compatible 3E frame. Follow the below screenshots as a reference for configuring this driver. *Note: Make sure that the value of 255 is specified in the "Address" field of the IODevice. The port no in Citect is entered in a decimal format and in
hexadecimal in the PLC.
|
Keywords: |
MELSECQ, Mitsubishi, Q03UDECPU |
Related Links
Attachments