Applies To:
  • CitectSCADA v7.10 spk 2 
Summary:

HF710SP246218 for CitectSCADA version 7.10 service pack 2

Bug 42645 - Citect reports can produce hardware alarms such as “Cicode type mismatch” and fail to produce correct output

At compile-time, incorrect Cicode variable references can be produced for Citect reports. The incorrect reference effectively
generates a reference to a variable outside the expected report which may be of the wrong type and would lead to the
“Cicode type mismatch” symptom. However, if the incorrect reference happened to reference a variable of the correct type,
a report might change the value of variables of other reports.


Files Affected:
Client.dll                             copy to _ProgramFilesFolder_\Citect\CitectSCADA 7.10\Bin\Client.dll
CtCmp32.exe                            copy to _ProgramFilesFolder_\Citect\CitectSCADA 7.10\Bin\CtCmp32.exe
CitectSCADAWebClient_7_10_2_14.cab     web client\server