On upgrade from V6.x to V7 my button font sizes have changed and are either too small or too large for the button.

In v7.x Button object text uses windows fonts and not Citect Fonts. If in the v6 project you used pixel sized fonts rather than point sizes which the button text Windows fonts use when upgrading CitectSCADA will use an approximate equivalent point sizes. This can result in fonts being either smaller or larger than previously. To resolve this the fonts used for buttons should be change from pixel to point size in the V6 project and the project re-upgraded. This is done by adding a minus sign before the size as in '-15'. If this is not possible then buttons can be changed manually on every page or graphics automation used.