HF710SP146384.1 for CitectSCADA version
7.10 service pack 1. Make sure you have the required version installed before applying this update. - Bug 43037 - Alarm Servers do not send property updates correctly and do not re-establish redundancy after comms interruption Bug 44100 - Acknowledged, cleared alarms remain active on redundant server after startup and synchronisation Bug 44678 - Alarm High value property is not being transmitted to the redundant server Bug 44839 - Alarm history not read from redundant server if current server does not have alarm save files and both servers are shutdown Bug 44929 - Write ALMINDEXSAVE.DAT in full rather than append when writing ALMSAVE.DAT to avoid any possibility of index duplication Bug 44745 - Cannot write to Delay property of Digital Alarm at Run time |
Files Affected: |
AlarmServer.dll copy to _ProgramFilesFolder_\Citect\CitectSCADA 7.10\Bin\AlarmServer.dll |