Applies To:
  • CitectSCADA V7.x

Summary:
 Alarm sounds will only sound once after an alarm is triggered belonging to an alarm category that has a priority but no alarm sound. In this case the alarm is displayed on the alarm summary page only so it can't be acknowledged and therefore the sounds stop working.

Solution:
 On the ON Action of the alarm category add the Cicode function AlarmAck(2, category number). This will ensure any Summary Page only alarms with a priority will be automatically acknowledged and alarm sounds will work as expected.

Keywords:
 alarm sounds, audible alarms, category, summary, active, page