Applies To: |
|
Summary: |
If you have a Citect project which is communicating to a Mitsubishi PLC using the MELSCNET driver and try to start the Historian while the I/O Device is offline, the Citect runtime may crash. |
Solution: |
This has been identified as a problem with the MELSCNET driver versions 2.02.09.000 and older. A fix has been produced and is available in MELSCNET Hotfix driver version 2.2.10.001. Please contact Global Support if you are experiencing this issue and require a hotfix driver. |
Keywords: |
MELSCNET, Historian |