11.1.93    <SHIFTDTRD>RIGHT

Description:   Used on Data Log Trend Display. Shifts displayed Data to right (forward in time).

Syntax:         <SHIFTDTRD>RIGHT                       

Arguments:    ^s^m^h^d

Examples:      <SHIFTDTRD>RIGHT^s^m^h^d

<SHIFTDTRD>LEFT^s^m^h^d and <SHIFTDTRD>RIGHT^s^m^h^d can be used to specify how Trend/XYplot display window shifts. For example, <SHIFTDTRD>LEFT^S^S^S^S will shift display window for second/minute/hour/ day interval type a full span to the left, <SHIFTDTRD>LEFT^Q^Q^Q^Q will shift display window for second/minute/hour/day interval type 1/4 span to the left, and <SHIFTDTRD>LEFT^1^1^1^1 will shift display window for second/minute/hour/day interval type 1 interval to the left.

The s/m/h/d value in <SHIFTDTRD>LEFT^s^m^h^d and <SHIFTDTRD>RIGHT^s^m^h^d can be negative. For example, <SHIFTDTRD>LEFT^-1^-1^-1^-1 will shift display window for second/minute/hour/day interval type x second/minute/hour/day to the left, where x is interval for the trend display. For 20 seconds interval trend, shifting will be 20 seconds to the left.