22.2.15         Changes not downloaded to SCADA node

Symptom

Adding new Tags, new Users or change existing Tags and Users in the WebAccess Project Manager, then Download to SCADA node, the changes don't appear on the SCADA node.


Cause

The creation of the run-time database (ARRANGE) is being interrupted.


Diagnostic

To verify the security settings on the ARRANGE subfolder:

1.       Open Windows Explorer (Right Click Start -> Explore).

2.       Browse to Drive:\WebAccess\Node\arrange

3.       Click on Arrange.

4.       Verify that there is a subdirectory with your projectname_nodename.

5.       Verify that the files in those subdirectories have today's date.

 

No subdirectories or old file dates in the ARRANGE subfolder

If there are no files in the project subfolder or the File Dates are old, the security setting on Drive:\WebAccess\Node\arrange is set to either Read-Only or denies access by the software.

1.       Right Click on the Arrange folder

2.       Select Properties

3.       Select the General tab

4.       Verify the folder is NOT Read Only

5.       Select the Security tab.

6.       Verify that Authenticated Users have Full Control

7.       If not Add Authenticated Users with Full Control.

8.       Click OK.

 Access Denied to the ARRANGE subfolder

If you get "Access Denied" to the Arrange folder, the ownership of the Arrange subdirectory is incorrect or corrupt.

1.       Right Click on the Arrange folder

2.       Select Properties

3.       Select the Security Tab

4.       Select the Advanced Button at the bottom of the Security Tab.

5.       Select the Owner tab

6.       Select Take Ownership of this folder

7.       Select OK

8.       From Security Tab, Verify that Authenticated Users have Full Control

9.       If not Add Authenticated Users with Full Control.

10.   Click OK

Problem: Download Graph from WebAccess Icon does not work.  Graphics and scripts not update.

Possible Causes:

1.      UNDERSCORE used in Project Name. 

WebAccess appends the ProjectName_NodeName using and underscore.  If you use an underscore in the Project name, WebAccess gets confused and will interpret the characters before the underscore (_) as the project name.

2.      Remote Access Code mismatch.  This occurs frequently when WebAccess is reinstalled and either an incorrect or no remote Access code was entered the second time.

Solution:

1.      Rename Your Project.

2.      Re-install WebAccess with correct remote access code.  This is recommended if you have many users using this SCADA node to save time in notifying them all.

Alternatively, use update to update your project to match the new remote access code entered during the install.  This might be faster if you are the only user.