4.3.25.1         1-bit, 2-state On-Off type Digital Tag example

This example shows the value of a typical digital Output tag. It has two states, Run and Stopped.  The tag controls a Supply Fan to an air handler unit.  Modbus Protocol is used.

Tag Type

Point  (discrete)

Tag Name

FAN_START101  

Description

AHU 101 Supply Fan  

Scan Type

Constant Scan  

Address

00101  

Conversion Code

Unsigned Integer

Start Bit

1  

Length

1  

Signal Reverse

No  

Log Data

No  

Data Log DB

0  

Write Change Log

Yes  

Read Only

No  

Keep Previous Value

No  

Value

0  

Security Area

0  

Security Level

0  

State 0

STOP  

State 1

RUN  

State 2

Not Used  

State 3

Not Used  

State 4

Not Used  

State 5

Not Used  

State 6

Not Used  

State 7

Not Used  

Array Size

0  

Alarm Data

 

Alarm Priority

1  

Alarm State

0  

Alarm Graph

2ductAHU  .bgr