This tag shows and controls the 8 states of a chiller, which range from Stopped to Hold to Run Fast to Vibration Alarm.
Note that the Modbus Protocol requires the 30001 or 40001 range of addresses if more that one bit is read.
Tag Type |
Point (discrete) |
Tag Name |
Chiller_7 |
Description |
Chiller No. 7 Control |
Scan Type |
Constant Scan |
Address |
40007 |
Conversion Code |
Unsigned Integer |
Start Bit |
0 |
Length |
3 |
Signal Reverse |
No |
Log Data |
No |
Data Log DB |
0 |
Write Change Log |
Yes |
Read Only |
No |
Keep Previous Value |
No |
Value |
0 |
Security Area |
0 |
Security Level |
0 |
State 0 |
STOPPED |
State 1 |
STOPPING |
State 2 |
HOLD |
State 3 |
STARTING |
State 4 |
RUN SLOW |
State 5 |
RUN MED |
State 6 |
RUN FAST |
State 7 |
VIB_ALARM |
Array Size |
0 |
Alarm Data |
|
Alarm Priority |
1 |
Alarm State |
7 |
Alarm Graph |
.bgr |
.