GetRegValue

Gets a the value of a variable in the Windows registry.

Function Group Execution Windows Embedded Thin Client
GetRegValue System Info Synchronous Supported Supported Not supported

Syntax

GetRegValue( numMainKey, strKey, strValueName )
numMainKey
Numeric tag with the following possible values:
0 HKEY_LOCAL_MACHINE
1 HKEY_CLASSES_ROOT
2 HKEY_CURRENT_USER
3 HKEY_USERS
4 HKEY_CURRENT_CONFIG
5 HKEY_PERFORMANCE_DATA
strKey
Path where the value is located in the Main Key.
strVariableName
Name of the variable to get. The maximum length is 255 characters.

Returned value

If the function succeeds, then the function returns the variable value. Otherwise one of the following error codes will be returned:

−1 Invalid number of parameters or invalid Main Key.
−2 Variable type is not supported. You can only read DWord or String values from the registry.
−3 Failed to read the variable value; verify that you have the proper security rights.

Examples

Tag Name Expression
Tag GetRegValue( 0, "HARDWARE\DESCRIPTION\System", "SystemBiosDate" ) // Returned value = "08/14/03"