These Tests are using an application that contains the DAY_TIME block and the TON block.
with "1" for the input of the first one which gives the date in
the output
with "2" for the input of the second one which gives the current
time in the output
The 2 outputs are concatenated with a bloc CAT that is connected to
an output variable.
Beginning of test 31-December-1999 at 23h59min50sec
End of the test 01-January-2000 at 00h02min
DOS -> OK
OS9
-> OK
DOS -> OK
OS9
-> OK
NT -> DAY_TIME not implemented
and TON test
OK
Vxworks->
Year2000 tests are not
possible on that system because there is no notion of
date.
DOS -> OK
OS9 -> OK
NT -> DAY_TIME not implemented and TON test OK
Vxworks-> Year2000 tests are not possible on that system because there is no notion of date.
ISaGRAF 3.00-> test OK (the project
is not recompiled)
ISaGRAF 3.20-> test OK (the project
is not recompiled)
ISaGRAF 3.31-> test OK (the project
is not recompiled)
ISaGRAF 3.00-> test OK (all programs
are not compiled. only the modified program is compiled)
ISaGRAF 3.20-> test OK (all programs
are not compiled. only the modified program is compiled)
ISaGRAF 3.31-> test OK (all programs
are not compiled. only the modified program is compiled)
ISaGRAF 3.00:
check of the dates in the project descriptor (creation of the project in 2000)
-> error, dates are written: 28/04/100 11:11:49 instead of 28/04/00
ISaGRAF 3.20:
check of the dates in the History of modifications (creation of a project in 2000)
-> error, dates are written: 28/04/100 11:11:49 instead of 28/04/00
Print of the History of modifications
-> error, dates are written: 28/04/100 11:11:49 instead of 28/04/00
check of dates in the project descriptor (creation of a project in 2000)
-> error, dates are written: 28/04/100 11:11:49 instead of 28/04/00
ISaGRAF 3.31:
check of the dates in the History of modifications (creation of a project in 2000) -> test OK
Print of the History of modifications -> test OK
check of dates in the project descriptor (creation of a project in 2000) -> test OK