Important: There are some differences in how
data is identified between the CIMPLICITY and the real-time
Collector.
The following lists define how data is mapped from CIMPLICITY to Historian to resolve these differences.
DATA_Log migration mapping. |
|
ALARM_LOG and EVENT_LOG migration mapping. |
|
Mapping guidelines. |
DATA_LOG migration mapping
The Historian Migration utility maps data from the CIMPLICITY DATA_LOG to Historian as follows.
Quality mapping |
|
Data Type mapping |
|
Point/Tag attributes mapping |
|
Data attribute mapping |
Quality Mapping
CIMPLICITY |
Historian |
and STALE=FALSE |
Good, ihOPCNonspecific |
IS_AVAILABLE and IS_IN_RANGE and STALE=TRUE |
Good, ihOPCLastKnowValue |
NOT IS_AVAILABLE |
Bad, ihOPCCommFailure |
NOT IS_IN_RANGE |
Bad, ihOPCOutOfService |
No effect on Historian quality No effect on Historian quality No effect on Historian quality |
|
USER Quality flags |
Bad, ihOPCNonspecific |
Data Type Mapping
CIMPLICITY Point Types |
Historian Data Type |
BOOL SINT INT USINT |
Integer Double integer Double integer Double integer |
REAL UDINT |
Double float Double float |
DINT UINT |
Double Integer Double Integer |
STRING STRING_20 STRING_8 STRING_80 |
Variable String Variable String Variable String Variable String |
3D_BCD 4D_BCD BYTE |
Not supported Not supported Not supported |
Point/Tag Attribute Mapping
CIMPLICITY |
Historian |
Point_id |
Tagname |
_ENG |
Engineering Units |
FROM SQL Table |
DataType |
Data Attribute Mapping
CIMPLICITY |
Historian |
Timestamp |
Timestamp |
_VAL |
Value |
_QUALITY |
Quality |
Note: Hi and Lo Engineering Units do not exist
in CIMPLICITY SQL table; these fields are ignored during the
migration.
ALARM_LOG and EVENT_LOG migration mapping
During the Historian migration fields in the ALARM_LOG and EVENT_LOG are mapped to be consistent with fields provided by the OPC Alarm & Event server.
CIMPLICITY |
Historian |
alarm_message |
Description |
Project, resource, alarm_id |
Source (project/resource/alarm_id) |
timestamp |
TimeStamp |
generation_time |
Endtime Condition Subcondition Event Category |
HIGH,MED,LOW,$SYS |
Severity Quality |
Mapping Guidelines
AlarmType is as follows.
AlarmType |
When read from |
ihALARM_CONDITION |
ALARM_LOG table |
ihALARM_SIMPLE |
EVENT_LOG table |
Condition and SubCondition are as follows.
For the: |
Condition and Subcondition |
Alarm log |
Exist, only for the Alarm log. |
Tag alarm |
Are set to Level to match the real time collector. |
System tag |
Use System. |
EventCategory use the following.
For the: |
EventCategory |
Tag alarm |
Level" |
System alarm |
System |
Severity is configurable by user.
Default mapping is as follows.
CIMPLICITY |
Historian |
HIGH $SYS |
850 |
MED |
500 |
LOW |
150 |
DataSource is PEAE_MIGRATION.
Source is combination of project/resource/alarm_id.
Proficy Historian migration. |