Dump XT Configuration

A DX9100 may have one or more extension (XT) modules installed. Use the Dump XT configuration option to query the currently selected device for its XT configuration and report it to the screen.

In the report:

X corresponds to an installed input/output point.

- corresponds to an input/output point which is not installed.

For example, there are two XT modules.

The first module has 8 analog points: 6 inputs and 2 outputs. For this module, AI[9] through AI[14] are valid input addresses and AI[15] through AI[16] are valid output addresses.

The second module has 8 binary points: four inputs and four outputs. For this module, BI[17] through BO[20] are valid input addresses, and BO[21] through BO[24] are valid output addresses.

The report to the screen looks like this:

XT 1            Analog                      Binary

        09 10 11 12 13 14 15 16     09 10 11 12 13 14 15 16

  In    X  X  X  X  X  X  –  –      –  –  –  –  –  –  –  –

  Out   –  –  –  –  –  –  X  X      –  –  –  –  –  –  –  –

XT 2            Analog                      Binary

       17 18 19 20 21 22 23 24      17 18 19 20 21 22 23 24

  In    –  –  –  –  –  –  –  –      X  X  X  X  –  –  –  –

  Out   –  –  –  –  –  –  –  –      –  –  –  –   X  X  X  X

More information

Installation verification procedures.