A DX9100 may have one or more extension (XT) modules installed. Use the Dump XT configuration option to query the currently selected device for its XT configuration and report it to the screen.
In the report:
X corresponds to an
installed input/output point.
- corresponds to an
input/output point which is not installed.
For example, there are two XT modules.
The first module has 8 analog
points: 6 inputs and 2 outputs. For this module, AI[9] through
AI[14] are valid input addresses and AI[15] through AI[16] are
valid output addresses.
The second module has 8 binary
points: four inputs and four outputs. For this module, BI[17]
through BO[20] are valid input addresses, and BO[21] through BO[24]
are valid output addresses.
The report to the screen looks like this:
XT 1 Analog Binary
09 10 11 12 13 14 15 16 09 10 11 12 13 14 15 16
In X X X X X X – – – – – – – – – –
Out – – – – – – X X – – – – – – – –
XT 2 Analog Binary
17 18 19 20 21 22 23 24 17 18 19 20 21 22 23 24
In – – – – – – – – X X X X – – – –
Out – – – – – – – – – – – – X X X X
Installation verification procedures. |