On the Device tab in the Point Properties dialog box:
Update Criteria |
The update criteria determines how the data will be collected and/or updated in your CIMPLICITY software application. |
|
Enter On Change or On Scan for points whose values should be polled by Mitsubishi TCP/IP communications at regular intervals. |
|
Enter On Demand On Scan or On Demand On Change for points whose values should be polled by Mitsubishi TCP/IP communications at regular intervals while users are viewing them. |
|
Enter Unsolicited for points that are sent by the programmable controller from the Fixed Buffer. |
Address |
Enter the point address of the data using the following format: <DEVICE_TYPE><OFFSET> |
|
For some device types, the offset is a hexadecimal number, while in other cases, the offset is a decimal number. |
|
Use the table below to determine how to specify your device and offset. |
|
Device Name |
Device Type |
Offset |
|
Data Register |
D |
Decimal |
|
Link Register |
W |
Hex |
|
Files Register |
R |
Decimal |
|
Timer (three types) |
|
|
|
Present Value |
TN |
Decimal |
|
Contact |
TS |
Decimal |
|
Coil |
TC |
Decimal |
|
Counter (three types) |
|
|
|
Present Value |
CN |
Decimal |
|
Contact |
CS |
Decimal |
|
Coil |
CC |
Decimal |
|
Input |
X |
Hex |
|
Output |
Y |
Hex |
|
Internals |
M |
Decimal |
|
Link Relay |
B |
Hex |
|
Annunciator |
F |
Hex |
|
Random Access |
Z |
Hex |
Unsolicited Communication via the Fixed Buffer is also supported.
Note on Unsolicited Point Addresses. |
|
Note on Addressing Formats |
|
Mitsubishi TCP/IP point configuration. |