Option 3.2.2. Specify a Device Point Scan Rate

The components for specifying the scan rate are:

Base Rate

Minimum rate at which device points can be polled on the port.

Scan Rate

Is a multiple of the Base Rate.

Enter the frequency at which the CIMPLICITY device communications option will read this point's data, based on the port's Base Rate.

Example

The Base Rate is 5 seconds

The Scan Rate is set to 3.

The point is scanned every 15 seconds.

Note: If you define Trigger Settings for a point, the Scan Rate field is disabled.

More information

Step 3.2. Enter device point advanced device properties.