Point Requirements for Manual Server Redundancy

The point you create to determine when either data collection or the entire project should be transferred to the secondary server is very specific. It must meet four conditions. It must:

  1. Have the same name as the name of the device.

  2.  Be a Boolean point.

  3. Have two (2) elements (for example, the status of the device on the primary server and the status of the device on the secondary server).

  4. Be a global point.

More information

Manual redundancy overview.