You can create an RCO Profile using the text editor of your choice, or in the Runtime User Interface. In your profile, you can choose to add sites from one project or from multiple projects.
In order to connect to multiple projects, they must be enabled for broadcast over the network.
Open a text editor, for example Notepad.
Enter lines for the SYSTEM section, as follows
SYSTEM |
Enter |
Line 1 |
[SYSTEM] Where SYSTEM is the heading enclosed in brackets. This section specifies the configuration of the profile. |
Line 2 (Optional) |
AUTOMATICREFRESH=Yes or No Where |
|
Yes |
Enables the RCO UI to automatically refresh the decision list. (Default) |
|
No |
Disables the feature and force manual updates. |
Line 3 (Optional) |
REFRESHRATE= n Where n =Value in seconds to automatically refresh the decision list. Minimum value = 7 (Default) |
Line 4 |
NUMSITES=n Where n =The number of sites you plan to add to this profile.
|
Line 5 (Optional) |
DEFAULTSITE==\\PROJECT1\SITE1= Where \\PROJECT1\SITE1= is the fully qualified project name and site name of the control site that you want to automatically default to when you access the RCO UI using this profile. When this profile is accessed, the RCO UI will open directly to the control site designated in this field. |
Press Enter twice to leave a blank line between the sections.
Enter lines for the SITES section as follows.
SITES |
|
Line 1
|
[SITE] Where SITE is the heading enclosed in brackets. This section specifies the project or projects and their corresponding sites. |
Line 2 |
\\PROJECTNAME\SITENAME=\\PROJECT1\SITE1= Where \\PROJECT1 is the fully qualified project name SITE1 is the site name = (Optional) Enter a description after the = Note: The site names correspond to the names that display in the Tracker window left pane. |
Lines 3 - n |
Repeat entering all of the sites that should be included in the profile. |
Update the NUMSITES field with the accurate site count.
Caution: If the value of the
NUMSITES field is less than
the actual number of sites listed, the Search dialog box will only
display the number of sites indicated in the field. When updating
the profile using the text editor, be sure to update the
NUMSITES field with the
accurate site count.
Select File>Save to open the Save as dialog box.
Select the directory where the profile is to be stored.
In the File Name field, enter the name of the profile and .rui as the extension.
The file must be an .rui file.
Click Save to save your profile.
Example. Site names in a manually created profile. |
|
Step 4. Create or open an RCO profile. |