Series 90 TCP/IP Triplex Supported Memory Types

The Series 90 TCP/IP Communications enabler supports reading and writing point data to the PACSystems, Series 90-70, and Series 90-30 controllers.

 Note: If you add a block to a programmable controller or resize domains, you must stop and restart the Series 90 TCP/IP Communications enabler in order for it to see the changes.

Data may be read from the following memory types:

Memory Type

Description

Memory Type

Description

%AI

Analog Input Table

%R

Register Memory

%AQ

Analog Output Table

%S

System Fault Table

%G

Genius Seamless

%SA

Special Contacts A

%I

Discrete Input Table

%SB

Special Contacts B

%L

Local Memory *

%SC

Special Contacts C

%M

Discrete Internal

%T

Discrete Temporary

%Q

Discrete Output Table

%W

Bulk Memory

* %L may only be used on Series 90-70 and PACSystems PLCs only

** %W may only be used on PACSystems RX3i and PACSystems RX7i

 

Data may be written to the following memory types:

Memory Type

Description

Memory Type

Description

%AI

Analog Input Table

%M

Discrete Internal

%AQ

Analog Output Table

%Q

Discrete Output Table

%G

Genius Seamless

%R

Register Table

%I

Discrete Input Table

%T

Discrete Temporary

%L

Local Memory *

%W

Bulk Memory

* %L may only be used on Series 90-70 and PACSystems PLCs only

** %W may only be used on PACSystems RX3i and PACSystems RX7i

Note: Proficy CIMPLICITY supports domain sizes of up to 65536 (64K) bytes only; however %W can be configured to a maximum size of 5242880 words (10M bytes). Therefore, the entire %W memory range cannot be accommodated within one domain.

 Warning: Do not write data to the system registers (%S, %SA, %SB, and %SC). Doing so may interfere with the normal operation of the programmable controller.