Parameters > Citect.ini File Parameters > Page Parameters > [Page]ScanTime


Note: This parameter is modified by the Computer Setup Wizard as well as the Computer Setup Editor. Any value you enter into your project parameters will be overridden by that specified in the Wizard.

The Page ScanTime determines how often (in milliseconds) the Animator refreshes a graphics page at runtime.

A value of 250 indicates that the Animator will refresh the page 4 times per second.

Under some conditions, you might want to slow the update of your pages to reduce the CPU load on the Client computer. For example, you might want faster response on your main operator computers, while slowing the response time on manager computers.

Allowable Values: 1 to 60000 (milliseconds)

Default Value: 250